An RPZ, or reduced pressure zone assembly, protects the public water main from high-hazard connections: boiler feeds, chemical injection, car washes, medical and dental offices, and irrigation with fertilizer injection.

The test has three parts. First the tester checks that the relief valve opens at 2.0 psid or more. Then the first check is read, and it usually holds a differential of 5 psid or higher. Last, the second check is tested for tightness against backpressure.

A dripping relief port is the classic RPZ complaint. Most of the time a pebble or scale from a recent main break is holding the first check open. Sometimes the relief diaphragm itself has torn.

RPZ assemblies must sit above grade with open air under the relief port. One buried in a pit can flood and siphon dirty water back, which is why most codes forbid it.

Grizzly Backflow & Plumbing connects Amherst, TX property owners with testers who handle RPZ valve testing and backflow prevention paperwork for brands like Watts, Febco, Wilkins and Ames. Call (833) 990-5874.

How it works

Four steps to backflow testing in Amherst, TX

  1. 01

    Grab your notice

    Have the utility letter handy. It lists the device, serial number and due date.

  2. 02

    Talk it through

    Call (833) 990-5874. We go over the device type and the price before anything is booked.

  3. 03

    Test day

    A certified tester reads each check and the relief valve on a calibrated gauge.

  4. 04

    Report filed

    The report goes to your water utility, and you keep a copy for your records.

Coverage

Backflow Testing Services Across Amherst, TX

Backflow testing for the neighborhoods and ZIP codes around Amherst, TX.

ZIP codes we serve

79312

Backflow testing FAQs

Questions about backflow testing

Questions we hear most often about RPZ Valve Testing in Amherst, TX.

Talk to a person
How long does a backflow test take?
A residential PVB or double check test usually takes 20 to 30 minutes. Large commercial and fire line assemblies take longer.
Does my lawn sprinkler system in Amherst, TX need a backflow preventer?
Almost every US plumbing code requires one on irrigation, since fertilizer, pesticide and standing water at the heads can siphon back. The device type depends on local code and how the system is laid out.
Can a backflow preventer freeze?
Yes. Trapped water expands and can crack the bronze body or blow out the bonnet. Insulated enclosures, heat cable or draining the device for winter prevent it.
Do I need an expansion tank after installing a backflow preventer?
Often, yes. The device makes your plumbing a closed system, so heated water cannot expand back to the main and the water heater relief valve may start dripping.
Is fire sprinkler backflow testing different?
Yes. Along with the standard check valve test, NFPA 25 calls for an annual forward flow test on fire line backflow assemblies. Results often go to both the water utility and the fire authority.